UK Lux Level Guidance: Recommended Lighting Levels by Space

A British open-plan office lit by recessed ceiling panels with daylight from side windows

We work with a lot of businesses planning their interior lighting, and they often want to make sure they’ve got a planned space that is “bright enough”. In this article we’ll cover how to know if you’ve got enough lighting planned.

In general though there is no specific lux or lighting figure. Regulations only require “suitable and sufficient” lighting. Actual safety minimums are quite low, and higher targets are only set by design standards – not legal limits. There’s no lighting police that will turn up if your room is quite dark.

We typically advise customers to use common sense rather than lux measurements and so on. However, for full detail we’ve outlined all relevant sources and what they cover.

Below we’ll cover the safety minimums, design targets, the law, and the maths to work out what lights you need for your space.

Recommended Lux Levels by Space, and Where Each Figure Comes From

Lux is simply lumens per square metre, and two separate sets of figures get quoted for it.

The first is a safety rule. HSE’s guidance Lighting at Work (HSG38) gives minimum illuminances that stop people tripping, straining their eyes or missing a hazard. The second is a design target: the level people can work at comfortably for a full shift. Those come from BS EN 12464-1:2021 and the SLL Code for Lighting 2022, and they sit well above the minimum.

Here’s the HSG38 table as it appears in the guidance (p.27-28), with an average and a minimum never to be measured below at any point.

ActivityTypical locations / workAverage illuminanceMinimum measured
Movement of people, machines and vehiclesLorry park, corridors, circulation routes20 lux5 lux
Movement in hazardous areas; rough work needing no perception of detailSite clearance, excavation, loading bays, bottling and canning plant50 lux20 lux
Work requiring limited perception of detailKitchens, factories assembling large components, potteries100 lux50 lux
Work requiring perception of detailOffices, sheet metal work, bookbinding200 lux100 lux
Work requiring perception of fine detailDrawing offices, electronic component assembly, textile production500 lux200 lux

Source: [HSG38 Lighting at Work, HSE](https://www.hse.gov.uk/pubns/priced/hsg38.pdf) (second edition, 1997, free PDF). Where detail has to be seen to spot a hazard, HSG38 raises a movement-only area to the perception-of-detail level.

In the design side. Every row names its source, and none are legal requirements.

Space or taskLevelWhat it’s based on
Office, mainly screen-based work300 luxUniversity of Warwick H&S guidance (cites CIBSE LG7)
Office, mainly paper-based work500 luxUniversity of Warwick H&S guidance
Process control room300 luxHSE human factors guidance
Corridor or walkway50 luxHSE human factors guidance
Studying an engineering drawing750 luxHSE human factors guidance
Warehouse bulk storage / racking aisles100-200 / 150-300 luxWidely quoted industry practice, not traceable to a standard
Domestic garage or home workshop300-500 lux general, 750+ at the benchLEDSAVE practical advice, applying HSG38’s task-detail logic. Not a compliance figure

You may see 300 to 500 lux quoted as an HSE requirement for offices. The HSE figure, from HSG38, is actually 200 lux average. Both numbers are real: one is the safety floor, the other is the level at which the room is decent to work in.

What UK Law Actually Requires for Workplace Lighting

There’s no statutory lux figure anywhere in UK law. If someone tells you 200 lux is “the legal minimum”, that’s just guidance, not the law.

The duty sits in Regulation 8 of the Workplace (Health, Safety and Welfare) Regulations 1992:

  • 8(1) “Every workplace shall have suitable and sufficient lighting.”
  • 8(2) That lighting “shall, so far as is reasonably practicable, be by natural light.”
  • 8(3) Suitable and sufficient emergency lighting in any room where people are specially exposed to danger if the artificial lighting fails.

So where does HSG38 fit? HSE’s own catalogue page puts it plainly: “Following the guidance is not compulsory… But if you do follow the guidance you will normally be doing enough to comply with the law.” Meet the HSG38 figures and you’re on solid ground.

Worth knowing: HSE’s web guidance and HSG38 don’t always agree, so attribute whichever figure you use to the document it actually came from.

The other documents you’ll see in specifications are [BS EN 12464-1:2021](https://landingpage.bsigroup.com/LandingPage/Standard?UPI=000000000030385601) (which superseded the 2011 edition), the SLL Code for Lighting 2022, CIBSE/SLL LG7 2023 for offices, BS 5266-1:2025 for emergency lighting, and Building Regulations Part L Volume 2 (2022). Standards current as of July 2026.

Where the Light Lands Matters as Much as How Much

“My office is 500 lux” only means something once you say where.

BS EN 12464-1:2021 sets its levels for the task area rather than the room as a whole, and they’re maintained illuminance figures, so the average mustn’t drop below them however old the installation gets.

HSG38 (p.30) also caps how much two neighbouring areas can differ. Its worked example: a 500 lux interior next to a movement-only yard would nominally allow 20 lux outside, a 25:1 jump, so the area nearest the doorway has to be lit to 50 lux as a transition zone. The eye needs several seconds to adapt, and sudden contrast is a hazard.

To measure a space, take readings across a grid of points at working-plane height, the desk or bench rather than the floor. A phone app gets you in the right ballpark; a proper lux meter is what you want for a reading you’ll act on. Compare your average against the target, your lowest reading against HSG38’s minimum measured column, and note whether daylight was contributing.

How Many Lumens Per Square Metre Do You Need?

This part is where you need a calculator. One lux is one lumen spread over one square metre, so:

  1. Target lux × floor area = lumens needed on the working plane.
  2. Divide by a maintenance factor (0.8 is a common working assumption) to allow for dirt on the optics and minor light depreciation as the LEDs age.
  3. Divide by the lumen output of one fitting to get your fitting count.

A 40 m² workshop at a 500 lux target needs 20,000 lumens. Divide by 0.8 and you’re specifying around 25,000 installed lumens. At 5,000 lumens per fitting, that’s five fittings.

The extra 5,000 covers two things Green Business Light’s explainer on lux, lumens and watts sets out: not every lumen escapes the fitting, and output falls off over time. Design exactly on target and you’ll be under it within a few years. Our EcoBrite® T8 tubes produce 120 lumens per watt, so that’s still a modest electrical load.

Spaces We Get Asked About Most

Offices and meeting rooms

Design to the 300 lux screen-based / 500 lux paper-based split and treat HSG38’s 200 lux average as the floor. Most offices land on 600×600 panels because they drop into a standard ceiling grid. Match the fitting size to the grid so runs line up, then check the task areas once it’s live. Our ceiling panel range covers the common grid sizes.

Warehouses, factories and loading bays

No warehouse lighting regulation names a lux figure, and the levels quoted for racking aisles are industry practice rather than standard. Mounting height decides the fitting: high bay fittings for tall spans, low bay for lower roofs.

Garages and home workshops

A domestic garage isn’t a workplace in the regulatory sense, so treat these as practical numbers rather than compliance: 300-500 lux general, 750 lux or more over the bench. Before you add fittings, paint the walls white; reflectance does a surprising amount of the work. Our guide to lighting a garage or workshop covers layout, and surface-mounted batten fittings are the usual answer for open runs.

Corridors, stairs and escape routes

HSG38 puts circulation routes at 20 lux average, while HSE’s web guidance says 50 lux for a corridor. Design for the higher figure and watch the transitions at doorways and on stairs. Escape route illuminances come from BS 5266 and are a separate calculation, so our emergency lighting fittings cover maintained and non-maintained options.

A vertical scale of recommended lux levels from 0.3 lux for full moonlight up to 500 lux for paper-based office tasks

Frequently Asked Questions

What’s the difference between lux and lumens?

Lumens measure the total light a fitting produces. Lux measures how much of it arrives on a given surface. Spread 10,000 lumens over 20 m² and you get 500 lux; spread them over 50 m² and you get 200 lux. Same fitting, very different room.

Is 300 lux enough for an office?

For mainly screen-based work with light note-taking, yes. Warwick’s health and safety guidance gives 300 lux for that, rising to 500 lux where the work is mainly paper-based. If your staff read printed documents most of the day, design for 500.

Why do CIBSE lighting tables disagree?

Because many of them trace back to older editions. TLC Direct publishes a widely used table clearly labelled CIBSE Code for Interior Lighting, 1994. That code has been superseded twice; the current successor is the SLL Code for Lighting 2022. Check the date on any table before you specify from it.

Getting the Numbers Right on Your Own Project

UK law asks for lighting that’s suitable and sufficient, HSG38 sets the safety floor, and BS EN 12464-1 with the SLL Code set the levels people actually want to work under. Work out your target illuminance, multiply by floor area, allow for maintenance, then pick fittings that add up to the lumens you need. If you’re not sure what a space needs, call us on 01652 638840 or browse our commercial lighting range and spec it from there.